Technical Data Sheet ASW 15K-LT-G2 ASW 17K-LT-G2 ASW 20K-LT-G2
Input DC
Max PV array Power225000 WP STC 25500 WP STC 30000 WP STC
Max in put voltage 1100 V1100 V1100 V
MPP Voltage range/ rated input voltage150 V TO 1000 V/ 630 V150 V TO 1000 V/ 630 V150 V TO 1000 V/ 630 V
Main Input voltage 125 V125 V125 V
Initial Feed- in voltage15O V15O V15O V
Max Operating input current
26 A /26 A26 A /26 A26 A /26 A
Max short circuit current40 A / 40 A40 A / 40 A40 A / 40 A
Number of independent MPP inputs/ String per MPP input2/A:2; B:12/A:2; B:12/A:2; B:1
OUTPUT AC:
Rated active power15000 W17000 W20000 W
Max apparent AC Power15000 VA 17000 VA20000 VA
AC nominal voltage 220 V/ 380 V -230 V / 400 V -240 V/ 425 V220 V/ 380 V -230 V / 400 V -240 V/ 425 V220 V/ 380 V -230 V / 400 V -240 V/ 425 V
AC voltage range160 V TO 300 V160 V TO 300 V160 V TO 300 V
AC Grid frequency 50 HZ/ 45 HZ TO 55 HZ- 60 HZ TO 65 HZ50 HZ/ 45 HZ TO 55 HZ- 60 HZ TO 65 HZ50 HZ/ 45 HZ TO 55 HZ- 60 HZ TO 65 HZ
Rated grid frequency / rated grid voltage 50 HZ/ 230 V50 HZ/ 230 V50 HZ/ 230 V
Max Output Current 24 A 27.1 A 31.1 A
Power factor at rated active power111
Adjustable Displacement 0.8 overexcited to 0.8 underexcited 0.8 overexcited to 0.8 underexcited 0.8 overexcited to 0.8 underexcited
feed-in phase 3 3 3
Harmonic Distortion (THD) at rated out put <3%<3%<3%
Efficiency and Protection
Max efficiency / European efficiency98.6 % / 98.2 %98.6 % / 98.2 %98.6 % / 98.2 %
DC Isolator
Ground fault monitoring
grid monitoring
CS reverse polarity protection/ AC Short circuit current capability.
ALL-pole- sensitive residual- current monitoring unit
Protection class( according ti IEC 62109-1)/ overvoltage category( according to IEC 62109-1)I/AC: III; DC: III/AC: III; DC: III/AC: III; DC: II
General Data
Dimension ( w/h/ d)503/ 435/ 183 503/ 435/ 183 503/ 435/ 183
Weight 17.3 KG 18 .6 KG 18.6 KG
Operating temperature range-25 C -+60 C -25 C -+60 C -25 C -+60 C
Self Consumption (at night) <1W<1W<1W
Topology TransformerlessTransformerlessTransformerless
Cooling Concept Active cooling Active cooling Active cooling
Degree of protection ( according to IEC 60529IP65IP65IP65
Climatic category ( according to IEC 60721- 3-44K4H4K4H4K4H
Max permissible valuable for relative Humidity ( non- condensing)100%100%100%
Max operating altitude 3000 M3000 M3000 M
Features:
DC connectionPhoenix contact Phoenix contact Phoenix contact
AC connection plug- in connector plug- in connector plug- in connector
MOUNTING TYPEwall-mount bracketwall-mount bracketwall-mount bracket
LED indicator ( status/ Fault/ Communication wi-Fi/ Rs485wi-Fi/ Rs485wi-Fi/ Rs485
Communication interface
Certificate ad approvals ( more available on request)
CE,EN 50549, 1EC 62109, IEC 62116, IEC 61727, IEC 616 83, IEC 60068, 1EC 60068,IEC 6100,AS/NZS4777,C10/C11CE,EN 50549, 1EC 62109, IEC 62116, IEC 61727, IEC 616 83, IEC 60068, 1EC 60068,IEC 6100,AS/NZS4777,C10/C11CE,EN 50549, 1EC 62109, IEC 62116, IEC 61727, IEC 616 83, IEC 60068, 1EC 60068,IEC 6100,AS/NZS4777,C10/C11